Your browser doesn't support javascript.
loading
Problems With Medical Gas Fitting in Great Earthquake Disaster / 日本農村医学会雑誌
Journal of the Japanese Association of Rural Medicine ; : 710-714, 2013.
Article in Japanese | WPRIM | ID: wpr-374348
ABSTRACT
  The water supply system in our hospital was disabled as its elevated water tank was badly damaged by the earthquake that hit northeast Japan on March11, 2011. Subsequently, the dysfunction of suction equipment of a water seal type threw the whole hospital into utter confusion, though temporarily. We realized that injection of some degree of water could recover the suction system on manual. To minimize the damage from a natural disaster and strengthen the hospital ability for all contingencies, we have decided to employ the oil rotary type rather than the water seal type in the system of suction equipment.
Full text: Available Index: WPRIM (Western Pacific) Language: Japanese Journal: Journal of the Japanese Association of Rural Medicine Year: 2013 Type: Article

Similar

MEDLINE

...
LILACS

LIS

Full text: Available Index: WPRIM (Western Pacific) Language: Japanese Journal: Journal of the Japanese Association of Rural Medicine Year: 2013 Type: Article