Investigation of Legionella Pollutionin in Central Air Conditioning System and Secondary Water Supply System in Public Places in Jiangxi Province / 环境与健康杂志
Article en Zh | WPRIM | ID: wpr-545405
Biblioteca responsable: WPRO
ABSTRACT
Objective To konw the Legionella contamination in the central air condition system and secondary water supply system in the public places of Jiangxi province. Methods 145 water samples were collected from the public places with central air conditioning system and secondary water supply system, in July to September in 2005-2006. Bacteria culture, hemagglutination test and duplex PCR test were used to identify Legionella. Results 15 Legionella strains was isolated from 145 samples, the positive rate was 10.34%, 7 Legionella strains was isolated from 78 samples of central air conditioning system, the positive rate was 8.97%, 8 Legionella strains was isolated from 57 samples of secondary water supply system,the positive rate was 14.04%. Conclusion It is necessary to strengthen the surveillance of Legionella in central air conditioning system and secondary water supply system.
Palabras clave
Texto completo: 1 Índice: WPRIM Idioma: Zh Revista: Journal of Environment and Health Año: 2007 Tipo del documento: Article