Analysis of Air Supply Quality of Central Air-conditioning Ventilation System in Building before and after Cleaning / 环境与健康杂志
Journal of Environment and Health ; (12)1992.
Artículo en Chino | WPRIM | ID: wpr-547519
ABSTRACT
Objective To know the air supply quality of central air-conditioning ventilation system in building before and after cleaning.Methods Three sets of central air-conditioning ventilation systems were selected from a building randomly and 3 air supply ways were selected in each system for the determination of inhalable particulate matter(PM10) and microorganisms in air before and after cleaning.Results After cleaning,the unqualified rate of air quality increased from 11.1%(before cleaning) to 77.8%.The mean value of PM10 increased from 0.051 mg/m3(before cleaning) to 0.083 mg/m3,the median of total account of bacteria and fungus increased from 150 cfu/m3 and 13 cfu/m2(before cleaning) to 570 cfu/m3 and 110 cfu/m3 respectively.Conclusion The air supply quality of central air-conditioning ventilation system in building may be damaged by cleaning if the operation is not in the right way.

Texto completo: Disponible Índice: WPRIM (Pacífico Occidental) Idioma: Chino Revista: Journal of Environment and Health Año: 1992 Tipo del documento: Artículo