Simultaneous detection of Legionella species and Legionella pneumophila by duplex PCR (dPCR) assay in cooling tower water samples from Jakarta, Indonesia.
Artigo
em Inglês
| IMSEAR
| ID: sea-148949
ABSTRACT
Aim:
Since culture method is time-consuming and has low sensitivity, we developed a duplex PCR (dPCR) assay for the detection of Legionella sp. and L. pneumophila in cooling tower samples. We used culture method as a gold standard.Methods:
Optimization of dPCR method was performed to obtain an assay with high sensitivity and specifi city. The optimized method was used to detect Legionella sp. dan L. pneumophila in 9 samples obtained from 9 buildings in Jakarta. For culture method, the bacteria were grown or isolated on selective growth factor supplemented-buffered charcoal yeast extract (BCYE) media.Results:
Of 9 samples tested by dPCR assay, 6 were positive for Legionella species,1 was positive for L. pneumophila, and 2 showed negative results. For the same samples, no Legionella sp. was detected by the culture method.Conclusion:
dPCR assay was much more sensitive than the culture method and was potentially used as a rapid, specifi c and sensitive test for routine detection of Legionella sp. dan for L. pneumophila in water samples.