ABSTRACT
Objective To evaluate the efficiency of control measures of the noise from a boiler room. Methods The main noise sourcs of the boiler room for attendant apartment near Wuhu railway station including air-blower and water pump were isolated using sound absorptive materials,a kind of modified PVC as sound isulator.The noise levels of the operation table for boiler workers and rooms of attendant apartment were measured before and after adopting noise control measures,then were evaluated based on GB12348-1990,the Criteria for Evaluation on the Noise of Industrial Enterprises. Results The equivalent sound levels of day and night were 76.1 and 73.5 dB(A) for the operation table for boiler workers,68.4 and 54.6 dB(A) for rooms of attendant apartment before and after noise control. The noise levels of above two monitoring points met the requirement of GB12348-1990 after the noise control. Conclusion The modified PVC sound insulator could effectively screen the noise from the boiler room.

Texto completo: DisponíveL Índice: WPRIM (Pacífico Ocidental) Idioma: Chinês Revista: Journal of Environment and Health Ano de publicação: 1993 Tipo de documento: Artigo