Investigation on Sanitation Administration and Legionella pneumophila Contamination in Central Air Conditioning System of Public Places / 环境与健康杂志
Journal of Environment and Health
;
(12)1993.
Artigo
em Chinês
| WPRIM
| ID: wpr-548499
ABSTRACT
Objective To know the hygienic administration status of central air conditioning system(CACS)and the Legionella contamination of cooling water in public places; and to identify the risk factors for legionella contamination associated with hygienic administration measures of CACS. Methods One hundred and forty-eight public places with CACS were recruited and the hygienic administration status was investigated by questionnaire survey in Sep. 2008. The culture methods were used to identify Legionella in cooling water. Results Positive rate of Legionella pneumophila in cooling water was 68.1%, 65.1% and 66.7% respectively in the condition of disinfection, preservative (detergent) and regular examination of the cooling water. The positive rate of Legionella pneumophila in cooling water was 92%, 87.7% and 84.7% respectively without disinfection, preservative,detergent and regular examination of the cooling water. Conclusion Disinfection, preservative,detergent and regular examination of the cooling water can reduce Legionella contamination risk.
Texto completo:
DisponíveL
Índice:
WPRIM (Pacífico Ocidental)
Tipo de estudo:
Estudo prognóstico
Idioma:
Chinês
Revista:
Journal of Environment and Health
Ano de publicação:
1993
Tipo de documento:
Artigo
Similares
MEDLINE
...
LILACS
LIS