Your browser doesn't support javascript.
loading
Air Circumstance in Laminar Flow Operating Room in Beijing:A Crosssection Investigation of 18 Hospitals / 中华医院感染学杂志
Chinese Journal of Nosocomiology ; (24)2006.
Artigo em Chinês | WPRIM | ID: wpr-592150
ABSTRACT
OBJECTIVE To investigate the management and sanitation status of the air circumstance in laminar flow operating rooms of grade two and above hospitals in Beijing.METHODS Air surveillance methods,cleaning methods of intakes,cleaning status of pipelines and frequency of renewing filter systems were investigated through interviewing charge nurse of 18 hospitals by questionnaires.RESULTS 50.0% of pipelines had never been cleaned,14.3% of intakes had never been cleaned.Air surveillance method of all hospitals was using sedimentation,with a low sensitivity.The monitoring systems were poor in 50.0% of hospitals.CONCLUSIONS Now there is only requirements of construction standard of clean surgery region,lacking routine regulations and technologies of contamination controlling standard,nor available dynamic contamination controlling system.Potential hazard exists in routine regulations of laminar flow operating room and it demands for making contamination controlling standard urgently in hospitals.

Texto completo: DisponíveL Índice: WPRIM (Pacífico Ocidental) Idioma: Chinês Revista: Chinese Journal of Nosocomiology Ano de publicação: 2006 Tipo de documento: Artigo