Your browser doesn't support javascript.
Poor ventilation worsens short-range airborne transmission of respiratory infection.
Li, Yuguo; Cheng, Pan; Jia, Wei.
  • Li Y; Department of Mechanical Engineering, The University of Hong Kong, Hong Kong SAR, China.
  • Cheng P; Department of Mechanical Engineering, The University of Hong Kong, Hong Kong SAR, China.
  • Jia W; Department of Mechanical Engineering, The University of Hong Kong, Hong Kong SAR, China.
Indoor Air ; 32(1): e12946, 2022 01.
Article in English | MEDLINE | ID: covidwho-1494731
ABSTRACT
To explain the observed phenomenon that most SARS-CoV-2 transmission occurs indoors whereas its outdoor transmission is rare, a simple macroscopic aerosol balance model is developed to link short- and long-range airborne transmission. The model considers the involvement of exhaled droplets with initial diameter ≤50 µm in the short-range airborne route, whereas only a fraction of these droplets with an initial diameter within 15 µm or equivalently a final diameter within 5 µm considered in the long-range airborne route. One surprising finding is that the room ventilation rate significantly affects the short-range airborne route, in contrast to traditional belief. When the ventilation rate in a room is insufficient, the airborne infection risks due to both short- and long-range transmission are high. A ventilation rate of 10 L/s per person provides a similar concentration vs distance decay profile to that in outdoor settings, which provides additional justification for the widely adopted ventilation standard of 10 L/s per person. The newly obtained data do not support the basic assumption in the existing ventilation standard ASHRAE 62.1 (2019) that the required people outdoor air rate is constant if the standard is used directly for respiratory infection control. Instead, it is necessary to increase the ventilation rate when the physical distance between people is less than approximately 2 m.
Subject(s)
Keywords

Full text: Available Collection: International databases Database: MEDLINE Main subject: Respiratory Tract Infections / Ventilation / Air Pollution, Indoor / Air Microbiology / COVID-19 Type of study: Prognostic study Limits: Humans Language: English Journal: Indoor Air Journal subject: Environmental Health Year: 2022 Document Type: Article Affiliation country: Ina.12946

Similar

MEDLINE

...
LILACS

LIS


Full text: Available Collection: International databases Database: MEDLINE Main subject: Respiratory Tract Infections / Ventilation / Air Pollution, Indoor / Air Microbiology / COVID-19 Type of study: Prognostic study Limits: Humans Language: English Journal: Indoor Air Journal subject: Environmental Health Year: 2022 Document Type: Article Affiliation country: Ina.12946