Your browser doesn't support javascript.
Assessment of university classroom ventilation during the COVID-19 pandemic.
Peters, Thomas M; Rabidoux, David; Stanier, Charles O; Anthony, T Renee.
  • Peters TM; Occupational and Environmental Health, College of Public Health, University of Iowa, Iowa City, Iowa.
  • Rabidoux D; Occupational and Environmental Health, College of Public Health, University of Iowa, Iowa City, Iowa.
  • Stanier CO; Chemical and Biochemical Engineering, College of Engineering, University of Iowa, Iowa City, Iowa.
  • Anthony TR; Occupational and Environmental Health, College of Public Health, University of Iowa, Iowa City, Iowa.
J Occup Environ Hyg ; 19(5): 295-301, 2022 05.
Article in English | MEDLINE | ID: covidwho-1740663
ABSTRACT
Ventilation plays an important role in mitigating the risk of airborne virus transmission in university classrooms. During the early phase of the COVID-19 pandemic, methods to assess classrooms for ventilation adequacy were needed. The aim of this paper was to compare the adequacy of classroom ventilation determined through an easily accessible, simple, quantitative measure of air changes per hour (ACH) to that determined through qualitative "expert judgment" and recommendations from the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), and the American Conference of Governmental Industrial Hygienists (ACGIH)®. Two experts, ventilation engineers from facilities maintenance, qualitatively ranked buildings with classrooms on campus with regard to having "acceptable classroom ventilation." Twelve lecture classrooms were selected for further testing, including a mix of perceived adequate/inadequate ventilation. Total air change per hour (ACH) was measured to quantitatively assess ventilation through the decay of carbon dioxide in the front and rear of these classrooms. The outdoor ACH was calculated by multiplying the total ACH by the outdoor air fraction. The classrooms in a building designed to the highest ASHRAE standards (62.1 2004) did not meet ACGIH COVID-19 recommendations. Four of the classrooms met the ASHRAE criteria. However, a classroom that was anticipated to fail based on expert knowledge met the ASHRAE and ACGIH criteria. Only two classrooms passed stringent ACGIH recommendations (outdoor ACH > 6). None of the classrooms that passed ACGIH criteria were originally expected to pass. There was no significant difference in ACH measured in the front and back of classrooms, suggesting that all classrooms were well mixed with no dead zones. From these results, schools should assess classroom ventilation considering a combination of classroom design criteria, expert knowledge, and ACH measurements.
Subject(s)
Keywords

Full text: Available Collection: International databases Database: MEDLINE Main subject: Air Pollution, Indoor / COVID-19 Type of study: Observational study / Prognostic study / Qualitative research Limits: Humans Language: English Journal: J Occup Environ Hyg Journal subject: Occupational Medicine / Environmental Health Year: 2022 Document Type: Article

Similar

MEDLINE

...
LILACS

LIS


Full text: Available Collection: International databases Database: MEDLINE Main subject: Air Pollution, Indoor / COVID-19 Type of study: Observational study / Prognostic study / Qualitative research Limits: Humans Language: English Journal: J Occup Environ Hyg Journal subject: Occupational Medicine / Environmental Health Year: 2022 Document Type: Article