Your browser doesn't support javascript.
loading
Show: 20 | 50 | 100
Results 1 - 1 de 1
Filter
Add more filters










Database
Language
Publication year range
1.
Heliyon ; 10(12): e32845, 2024 Jun 30.
Article in English | MEDLINE | ID: mdl-38975111

ABSTRACT

Low voltage DC microgrids (LVDC) are on rise, because of increase in usage of electronics-based utility loads. However, the protection and safety aspects of these grids remain unresolved due to the fault current magnitude, unnecessary tripping, and blinding of protection. In this paper, an adaptive differential protection system incorporated with an advanced graph algorithm is proposed for DC microgrid. This graph algorithm is a combination of Fenwick tree and Bidirectional Dijkstra algorithm. Fenwick tree algorithm is used to determine the network configuration and Bidirectional Dijkstra algorithm is used to determine the least distance from the fault location to the nearest distributed generations. The developed protection scheme is applied to a 7 bus, 400 V DC microgrid setup using Real Time simulator (control hardware in loop) to detect and clear the faults such as kilometric faults, and cross-country faults. In terms of efficiency, the proposed algorithm demonstrates superiority over the conventional algorithm by detecting and rectifying faults in 384 µs.The results depict the robustness of the protection setup in clearing the faults rapidly with minimum network disconnection.

SELECTION OF CITATIONS
SEARCH DETAIL
...