Your browser doesn't support javascript.
loading
Show: 20 | 50 | 100
Results 1 - 1 de 1
Filter
Add more filters










Database
Language
Publication year range
1.
Water Sci Technol ; 64(3): 708-14, 2011.
Article in English | MEDLINE | ID: mdl-22097051

ABSTRACT

Legionella bacteria encounter optimum growing conditions in hot water systems and cooling towers. A pilot-scale 1 unit was built in order to study the biofilm disinfection. It consisted of two identical loops, one used as a control and the other as a 'Test Loop'. A combination of a bio-detergent and a biocide (hydrogen peroxide + peracetic acid) was applied in the Test Loop three times under the same conditions at 100 and 1,000 mg/L with a contact time of 24 and 3-6 hours, respectively. Each treatment test was preceded by a three week period of biofilm re-colonization. Initial concentrations of culturable Legionella into biofilm were close to 10(3) CFU/cm2. Results showed that culturable Legionella spp. in biofilm were no longer detectable three days following each treatment. evertheless, initial Legionella spp. concentrations were recovered 7 days after the treatments (in two cases). Before the tests, Legionella spp. and L. pneumophila PCR counts were both about 10(4) GU/cm2 in biofilm and they both decreased by 1 to 2 log units 72 hours after each treatment. The three tests had a good but transient efficiency on Legionella disinfection in biofilm.


Subject(s)
Biofilms , Disinfectants/pharmacology , Hot Temperature , Hydrogen Peroxide/pharmacology , Legionella/drug effects , Peracetic Acid/pharmacology , Water Microbiology , Pilot Projects , Polymerase Chain Reaction
SELECTION OF CITATIONS
SEARCH DETAIL
...