1.
Zentralbl Hyg Umweltmed ; 196(5): 444-54, 1995 Jan.
Article in English | MEDLINE | ID: mdl-7727024

ABSTRACT

Corrosion damage in the copper cold-water plumbing system of a large building was investigated. An unusual combination of corrosion patterns was found on the inner copper pipe surfaces that were in contact with water. Damage was in the form of shallow cavities, a surface cover or pinprick-like pits. The corrosion system was influenced by thermal treatment and also by cefoxitin dosing. The latter fact in particular is a clear indication of microbiological involvement in this corrosive action. Different parameters, to be measured in standing water (24-h stagnation), are considered typical for this type of corrosion: the detection of Sphingomonas spec. and other species in whose cell wall regions copper can accumulate, a copper content of more than 2 mg/l, oxygen consumption of more than 4 mg/l and an increase in pH. With the help of these indicators, it is possible to recognize microbiologically induced corrosion in copper plumbing systems before pipe perforation occur.


Subject(s)
Bacteria/isolation & purification , Copper , Sanitary Engineering , Water Microbiology , Water Supply/standards , Bacteria/drug effects , Bacteria/metabolism , Cefoxitin/pharmacology , Copper/analysis , Disinfection , Germany , Hot Temperature , Humans , Quality Control , Sanitary Engineering/standards , Water Supply/analysis