RESUMO
Surveillance of Legionella spp. in hospital water systems was performed in forty-four inpatient healthcare facilities in Spain during 2005-2006. A total of 2,341 samples were collected: 470 from cooling systems (cooling towers) and 1,871 from potable water systems. The latter included 211 from cold-water tanks and 260 from hot-water tanks, totalling 471 from central water reservoirs 136 from showers, 1,172 from unfiltered taps and 92 from filtered taps, totalling 1,400 from peripheral points. Temperature, chlorine levels and the presence of Legionella spp. were determined. In all, 373 (15.9%) samples yielded Legionella spp. Significantly higher isolation rates were obtained from cooling towers (23.8%) versus cold- and hot-water tanks (approximately 4.7%), due to the significantly higher number of samples positive for serogroup 1 (19.4 vs 0.9-3.5%). In potable water systems, no differences were found between central water tanks and showers, but significant differences in isolation rates between central water tanks and unfiltered taps were observed (4.7 vs 19.6%) due to differences in non-serogroup 1 L. pneumophila. Filters significantly decreased isolation rates of these serotypes (11 vs 0%). Some seasonal differences were noted, with higher isolation rates in summer for legionella serogroup 1 in cooling systems and for L. pneumophila serogroups 2-14 in potable water systems. In regression models, higher temperatures were associated with colonisation in cooling systems, while lower chlorine levels were associated with colonisation in potable water systems.