Medidas de protección radiológica: implicaciones en el diseño de quirófanos de neurocirugía / Radiation protection measures: Implications on the design of neurosurgery operating rooms
Neurocirugía (Soc. Luso-Esp. Neurocir.)
; 29(4): 187-200, jul.-ago. 2018. ilus, tab, graf
Artigo
em Espanhol
| IBECS
| ID: ibc-180309
Biblioteca responsável:
ES1.1
Localização: BNCS
RESUMEN
Objetivo:
Describir pros y contras de diversas medidas de protección radiológica y sus implicaciones en el diseño de un quirófano de neurocirugía. Material ymétodos:
Se realizó una reforma estructural del quirófano de neurocirugía a propósito de la adquisición y uso de un O-arm. Se ampliaron las medidas y blindajes del quirófano, y se instaló una mampara blindada y abatible en su interior. Se midieron dosis de radiación delante y detrás de la mampara.Resultados:
La mampara proporciona una radioprotección integral para todo el personal de quirófano (dosis < 5μSv a 2,5 m del gantry por cada exploración con O-arm; 0,0μSv tras la mampara por cada exploración de O-arm; dosis acumulada anual tras la mampara, indetectable), obvia la necesidad de delantales plomados y dosímetros personales y minimiza la circulación de personal. El aumento del tamaño del quirófano permite almacenar los equipos dentro y minimiza el riesgo de colisión o contaminación. Los quirófanos rectangulares permiten aumentar la distancia al foco emisor de radiación.Conclusiones:
El blindaje de paredes, techos y suelos, la forma rectangular y la superficie lo más amplia posible, la presencia de una mampara plomada y abatible, y los sistemas de seguridad que impiden una irrupción inesperada en el quirófano mientras se está irradiando son cuestiones relevantes a tener en cuenta en el diseño del quirófano de neurocirugíaABSTRACT
Objective:
To describe pros and cons of some radiation protection measures and the implications on the design of a neurosurgery operating room. Material andmethods:
Concurring with the acquisition and use of an O-arm device, a structural remodeling of our neurosurgery operating room was carried out. The theater was enlarged, the shielding was reinforced and a foldable leaded screen was installed inside the operating room. Radiation doses were measured in front of and behind the screen.Results:
The screen provides whole-body radiation protection for all the personnel inside the theater (effective dose <5μSv at 2,5 m from the gantry per O-arm exploration; 0,0μSv received behind the screen per O-arm exploration; and undetectable cumulative annual radiation dose behind the screen), obviates the need for leaded aprons and personal dosimeters, and minimizes the circulation of personnel. Enlarging the size of the operating room allows storing the equipment inside and minimizes the risk of collision and contamination. Rectangular rooms provide greater distance from the source of radiation.Conclusion:
Floor, ceiling and walls shielding, a rectangular-shaped and large enough theater, the presence of a foldable leaded screen, and the security systems precluding an unexpected irruption into the operating room during irradiation are relevant issues to consider when designing a neurosurgery operating theater
Buscar no Google
Coleções:
Bases de dados nacionais
/
Espanha
Base de dados:
IBECS
Assunto principal:
Salas Cirúrgicas
/
Lesões por Radiação
/
Procedimentos Neurocirúrgicos
/
Traumatismos Ocupacionais
/
Arquitetura Hospitalar
Limite:
Humanos
Idioma:
Espanhol
Revista:
Neurocirugía (Soc. Luso-Esp. Neurocir.)
Ano de publicação:
2018
Tipo de documento:
Artigo
Instituição/País de afiliação:
Hospital Universitario de Burgos/España